is in the closed position. If the generator set fuel tank is being used,
the START-RUN-STOP switch should be placed in the RUN position and the
BATTLE SHORT switch in the ON position.
The fuel level gauge should be
checked for sufficient fuel indication. The START-RUN-STOP switch should be
left in the RUN position and the BATTLE SHORT switch in the ON position for
a sufficient length of time to ensure that the day tank assembly contains
enough fuel for starting. The BATTLE SHORT switch should then be turned to
the OFF position. The soldier should depress the fault location indicator
TEST OR RESET switch and check that all fault location indicator lights
illuminate. Finally, the soldier should pull the manual speed control all
the way out, and then push it approximately halfway back in.
b. Never allow soldiers to attempt to start the generator set if it is
not properly grounded.
Failure to observe this warning may result in
serious injury or death by electrocution.
Do not allow soldiers to crank
the engine in excess of 15 seconds. Allow the starter assembly to cool at
least 15 seconds between crankings.
2.
Your soldiers are now ready to start the generator.
a. Hold the START-RUN-STOP switch in the START position until the
engine oil pressure gauge indicates oil pressure and the voltmeter indicates
voltage.
Release the START-RUN-STOP switch to the RUN position.
If the
ambient temperature is below 50 degrees Fahrenheit, use of the start aid
assembly as follows may be required: Crank the generator set engine. Inject
a "shot" of ether into the air cleaner assembly by placing the engine primer
switch in the ON position, and then release.
cease operation and notify maintenance personnel.
RUN-STOP switch and allow the cranking motor to cool at least three minutes
prior to repeating the starting procedure.
Place the VOLTS/AMPS transfer
switch to the 416V operating position. Rotate the VOLTAGE ADJUST rheostat
until 416V is indicated on the AC voltmeter. Adjust frequency to 60 Hz as
d. If any of the indicator lights illuminate, stop the generator set
and correct the indicated fault before proceeding with operations.
e. Hold the circuit breaker switch in the CLOSE position until the
4-3