Temperature correction factor.
Delivery correction to 60 degrees Fahrenheit.
Meter factor. The meter factor equals the prover quantity at 60
degrees Fahrenheit divided by the meter quantity at 60 degrees
Fahrenheit divided by the meter quantity at 60 degrees Fahrenheit. The
factor is carried out to four (4) decimal places.
Meter certification record. The meter certification record in
conjunction with the meter test results is your proof that the meter has
been properly calibrated. The following items will be included in the
meter certification and recorded to ensure that the meter has been
properly tested and calibrated when required:
Date meter was verified.
Meter factor.
Was meter factor within .0025.
Verification adjustment:
Not
Performed Date__________
Required___________
Required but Not
______________________
Performed
If adjustment is required but not performed, the meter factor should
be used to adjust all issues or receipts through the meter.
Use of the meter verification record.
Remarks: Any repairs or adjustments to the meter should be recorded.
12-129
QM 5099